CB Boiler

|
- HEATING
or PROCESSING |
|
-
STEAM(15to450psi) or HOT WATER(30lbs.AND UP)
|
|
- 15 to
800 HORSEPOWER |
|
- OIL.,
GAS or COMBINATION |
|
-
ALTERNATE FUEL CAPABILITY |
|
- LOW NOx
CAPABILITY |
1. Fuel Cost
Savings and Fuel Conservation
The boiler with the
highest guaranteed fuel-to-osteam efficiency*
will burn least amount of fuel for the same output. You pay
your fuel bills based on the fuel-to-steam efficiency of
your boiler!
GUARANTEED
FUEL-TO-STEAM EFFICIENCIES ON MODEL CB FIRE TUBE BOILERS AT
50% AND 100% OF RATING
|
BOILER
SIDE(HP)
|
GAS FUEL
|
NO.2 OIL
|
NO.5 & NO.6 OILS
|
15#Design
10PSIG Operation
|
150#Design
10PSIG Operation
|
15#Design
10PSIG Operation
|
150#Design
125PSIG Operation
|
15#Design
10PSIG Operation |
150#Design
125PSIG Operation
|
|
% of Load
|
% of Load
|
% of Load
|
% of Load
|
% of Load
|
% of Load
|
|
|
50%
|
100%
|
50%
|
100%
|
50%
|
100%
|
50%
|
100%
|
50%
|
100%
|
50%
|
100%
|
|
100
|
83.5
|
83.5
|
80.5
|
81.0
|
86.5
|
86.5
|
80.5
|
81.0
|
84.0
|
87.0
|
84.0
|
84.5
|
|
125
|
82.0
|
82.0
|
79.0
|
79.5
|
85.0
|
85.5
|
79.0
|
79.5
|
82.5
|
86.0
|
82.5
|
83.5
|
|
150
|
83.0
|
83.0
|
80.0
|
80.5
|
86.0
|
86.5
|
80.0
|
80.5
|
83.5
|
83.5
|
83.5
|
84.5
|
|
200
|
83.5
|
83.5
|
80.5
|
81.5
|
87.0
|
87.0
|
80.5
|
81.5
|
84.5
|
84.5
|
84.5
|
85.0
|
|
250
|
82.0
|
82.0
|
79.5
|
80.0
|
85.5
|
85.5
|
79.5
|
80.0
|
83.5
|
80.0
|
83.5
|
83.5
|
|
300
|
82.5
|
82.5
|
80.0
|
80.5
|
86.0
|
86.0
|
80.0
|
80.5
|
84.0
|
80.5
|
84.0
|
84.0
|
|
350
|
83.0
|
83.0
|
80.5
|
81.0
|
86.5
|
86.5
|
80.5
|
81.0
|
84.5
|
81.0
|
84.5
|
85.0
|
|
400
|
83.0
|
83.0
|
80.0
|
80.5
|
86.0
|
86.5
|
80.0
|
80.5
|
84.0
|
80.5
|
84.0
|
84.5
|
|
500
|
84.0
|
84.0
|
81.0
|
81.5
|
87.0
|
87.5
|
81.0
|
81.5
|
84.5
|
81.5
|
84.5
|
85.5
|
|
600
|
84.0
|
84.5
|
81.0
|
82.0
|
87.5
|
87.5
|
81.0
|
82.0
|
85.0
|
82.0
|
85.0
|
86.0
|
|
700
|
84.5
|
84.5
|
81.5
|
82.0
|
87.5
|
88.0
|
81.5
|
82.0
|
85.0
|
82.0
|
85.0
|
86.0
|
|
800
|
84.5
|
84.5
|
81.5
|
82.0
|
88.0
|
88.0
|
81.5
|
82.0
|
85.5
|
82.0
|
85.5
|
86.0
|
*Fuel Heating Valves:
Natural Gas - 1,000 BTU/Cu.Ft.
#2 Oil - 140,000 BTU/Gal.
#5&6 Oil - 150,000 BTU/Gal.
*Fuel-to-Steam Efficiency
includes an allowance for Radiation and Convection boiler
heat losses from the Unit to the boiler room
SOUND
PRESSURE LEVEL SUMMARY
FIRE TUBE BOILERS 48" THRU 96" DIA.
Sound Pressure levels
measured on boilers operating in various
locations and expressed in dBA are as
follow
|
Boiler
|
CB-50
|
CB-60
|
CB-70
|
CB-80
|
CB-100
|
CB-125A
|
CB-125
|
CB-150
|
CB-200
|
|
HFO,dBA
|
79
|
79
|
79
|
79
|
81
|
82
|
83
|
83
|
83
|
|
LFO,dBA
|
78
|
78
|
78
|
78
|
79
|
79
|
81
|
82
|
81
|
|
HFG,dBA
|
77
|
77
|
78
|
78
|
78
|
79
|
81
|
80
|
82
|
|
LFG,dBA
|
72
|
73
|
74
|
75
|
75
|
75
|
78
|
77
|
78
|
|
Boiler
|
CB-250
|
CB-300
|
CB-350
|
CB-400
|
CB-500
|
CB-600
|
CB-700
|
CB-800
|
|
HFO,dBA
|
88
|
88
|
89
|
83
|
83
|
83
|
85
|
88
|
|
LFO,dBA
|
86
|
86
|
85
|
80
|
82
|
82
|
82
|
84
|
|
HFG,dBA
|
84
|
86
|
86
|
82
|
82
|
82
|
85
|
87
|
|
LFG,dBA
|
81
|
82
|
83
|
80
|
81
|
81
|
82
|
84
|
SOUND PRESSURE LEVEL SUMMARY : HF = HIGH
FIRE , LF = LOW FIRE , O = OIL , G = GAS
|
Picture and Information Property of Cleaver Brooks |
|